Dynamic Industrial Logic Pass Box Controller -- 2
Budget: ₹1,500 – ₹12,500 INR
dynamic pass box controller
Dynamic Pass Box Controller (Final Industrial Logic with HMI + HEPA Sensor)
System Description:
The system consists of:
• Two interlocked doors (Door-1 and Door-2)
• 7-inch resistive touch HMI (UART based)
• HEPA filter with differential pressure sensor (2 pipe type)
• UV light
• Blower system
• Buzzer alarm
________________________________________
Door Interlock Logic
• Door-1 and Door-2 must never open at the same time
• If Door-1 is open → Door-2 must remain locked
• If Door-2 is open → Door-1 must remain locked
________________________________________
Operation Sequence
1. User presses Door-1 button
2. If Door-2 is closed → Door-1 unlocks
3. After Door-1 closes → system starts process cycle
________________________________________
Process Cycle
• Blower ON
• UV Light ON
• Timer value taken from HMI
After timer complete:
• Blower OFF
• UV OFF
• Door-2 unlock
________________________________________
HMI Functions (Editable Settings)
• UV Time (0–999 sec)
• Blower Time
• Door Delay Time
• Alarm Time
• Pressure Setpoint (Pa)
________________________________________
Monitoring on HMI
• Real-time Pressure (Pa)
• Door Status (OPEN/CLOSE)
• System Status
________________________________________
HEPA Differential Pressure System
• Sensor: MPXV7002DP (low cost)
• Type: Dual port (2 pipe connection)
Connection:
• Port 1 → HEPA chamber
• Port 2 → Outside air
Signal:
• Analog output (0–5V) → MCU ADC
________________________________________
Alarm Conditions
• Pressure below setpoint → Alarm
• Both door open attempt → Alarm
• Door open too long → Alarm
Action:
• Buzzer ON
• Warning on HMI
________________________________________
Additional Features
• Manual mode (HMI control)
• Auto mode
• DWIN HMI DMG80480T070_01WTR | 7” | 800×480 | UART | 5V | Q
Madam,/sir this is the material list for reference, you can use any component as per your which should be low cost and good quality components.requirement
Controller Section (PCB SMD)
• ATmega328P-AU | TQFP-32 | 5V MCU | Qty: 10
• Crystal 16 MHz | SMD 3225 | Qty: 10
• Capacitor 22pF | SMD 0805 | Qty: 20
• Capacitor 0.1µF | SMD 0805 | Qty: 60
• Capacitor 10µF | SMD 1206 | Qty: 30
________________________________________
Power Supply
• SMPS 230VAC → 12V DC (2A) | Qty: 10
• AMS1117-5.0 | SOT-223 | Qty: 10
• Capacitor 1000µF / 25V | Qty: 20
• Capacitor 470µF / 25V | Qty: 10
• Diode M7 (SMD) | Qty: 30
________________________________________
Relay Control
• Relay SCS-5-DC12V | 12V | 10A | Qty: 50
• ULN2003A | SOP-16 | Qty: 10
________________________________________
Buzzer
• Active Buzzer 5V PCB Mount | Qty: 10
________________________________________
LED + Resistor (SMD 0805)
• LED Red | Qty: 20
• LED Green | Qty: 20
• LED Yellow | Qty: 20
• Resistor 220Ω | Qty: 60
• Resistor 1kΩ | Qty: 80
• Resistor 10kΩ | Qty: 120
________________________________________
• Password protected settings (optional)
BOM
Dynamic Pass Box Controller (Final Industrial Logic with HMI + HEPA Sensor)
System Description:
The system consists of:
• Two interlocked doors (Door-1 and Door-2)
• 7-inch resistive touch HMI (UART based)
• HEPA filter with differential pressure sensor (2 pipe type)
• UV light
• Blower system
• Buzzer alarm
________________________________________
Door Interlock Logic
• Door-1 and Door-2 must never open at the same time
• If Door-1 is open → Door-2 must remain locked
• If Door-2 is open → Door-1 must remain locked
________________________________________
Operation Sequence
1. User presses Door-1 button
2. If Door-2 is closed → Door-1 unlocks
3. After Door-1 closes → system starts process cycle
________________________________________
Process Cycle
• Blower ON
• UV Light ON
• Timer value taken from HMI
After timer complete:
• Blower OFF
• UV OFF
• Door-2 unlock
________________________________________
HMI Functions (Editable Settings)
• UV Time (0–999 sec)
• Blower Time
• Door Delay Time
• Alarm Time
• Pressure Setpoint (Pa)
________________________________________
Monitoring on HMI
• Real-time Pressure (Pa)
• Door Status (OPEN/CLOSE)
• System Status
________________________________________
HEPA Differential Pressure System
• Sensor: MPXV7002DP (low cost)
• Type: Dual port (2 pipe connection)
Connection:
• Port 1 → HEPA chamber
• Port 2 → Outside air
Signal:
• Analog output (0–5V) → MCU ADC
________________________________________
Alarm Conditions
• Pressure below setpoint → Alarm
• Both door open attempt → Alarm
• Door open too long → Alarm
Action:
• Buzzer ON
• Warning on HMI
________________________________________
Additional Features
• Manual mode (HMI control)
• Auto mode
• DWIN HMI DMG80480T070_01WTR | 7” | 800×480 | UART | 5V | Q
Madam,/sir this is the material list for reference, you can use any component as per your which should be low cost and good quality components.requirement
Controller Section (PCB SMD)
• ATmega328P-AU | TQFP-32 | 5V MCU | Qty: 10
• Crystal 16 MHz | SMD 3225 | Qty: 10
• Capacitor 22pF | SMD 0805 | Qty: 20
• Capacitor 0.1µF | SMD 0805 | Qty: 60
• Capacitor 10µF | SMD 1206 | Qty: 30
________________________________________
Power Supply
• SMPS 230VAC → 12V DC (2A) | Qty: 10
• AMS1117-5.0 | SOT-223 | Qty: 10
• Capacitor 1000µF / 25V | Qty: 20
• Capacitor 470µF / 25V | Qty: 10
• Diode M7 (SMD) | Qty: 30
________________________________________
Relay Control
• Relay SCS-5-DC12V | 12V | 10A | Qty: 50
• ULN2003A | SOP-16 | Qty: 10
________________________________________
Buzzer
• Active Buzzer 5V PCB Mount | Qty: 10
________________________________________
LED + Resistor (SMD 0805)
• LED Red | Qty: 20
• LED Green | Qty: 20
• LED Yellow | Qty: 20
• Resistor 220Ω | Qty: 60
• Resistor 1kΩ | Qty: 80
• Resistor 10kΩ | Qty: 120
________________________________________
• Password protected settings (optional)
BOM
Related categories:
Electronics
Microcontroller
PLC & SCADA
Electrical Engineering
Embedded Systems
Alarm Systems
Automation