Allen Bradley controller programming

Job ID: 36497474

Budget: $1,500 – $3,000 USD

I am looking for a freelancer who can program my MicroLogix Allen Bradley controller using Modbus communication protocol. The primary purpose of the controller program is for process control and monitoring. Ideal skills and experience for this job include:

- Proficiency in Allen Bradley programming
- Strong understanding of Modbus communication protocol
- Experience in process control and monitoring
- Ability to troubleshoot and debug code
- Attention to detail and ability to follow specifications closely

If you have the skills and experience necessary for this project, please submit a proposal. Thank you.

Some points about the project. (Info on attached documents as well.)

(PUMPS)
Circulation Pump (CWP) switch over to Backup Circulation Pump (BCWP), based on fault of pressure switches.
Time based sequencing to alternate between Circulation Pump (CWP) and Backup Circulation Pump (BCWP). With adjustable time (Controlled through Modbus).
Supply Pump (SP) switch over to Backup Supply Pump (BSP), based on fault of pressure switches.
Time based sequencing to alternate Supply Pump (SP) to Backup Supply Pump (BSP). With adjustable time (Controlled through Modbus).
SP and BSP pump speed from Variable frequency drive (VFD) via 0-10vdc.
High level switch and low level switch to cutout all pumps.

(CHILLERS)
Time based sequencing of Chill-A , Chill-B and Chill-C. With adjustable time (Controlled through Modbus).

(TANK)
H2O make-up solenoid valve to close if high tank level is recognized.

(RUN STATUSES)
Chill-A Run Status
Chill-B Run Status
Chill-C Run Status
CWP Run Status
BCWP Run Status
SP Run Status
SP Run Speed
BSP Run Status
BSP Run Speed

(FAULTS/ALARMS)
High Tank Temperature
Low Tank Level
High Tank Level
CWP Pressure Fault - Only if CWP is engaged
BCWP Pressure Fault - Only if BCWP is engaged
SP Pressure Fault - Only if SP is engaged
BSP Pressure Fault - Only if BSP is engaged

(MODBUS CONTORL)
CWP and BCWP Time sequencing set parameter
SP and BSP Time sequencing set parameter
Chiller time sequencing set parameter
Chill-A Set Point
Chill-B Set Point
Chill-C Set Point

(MODBUS MONITOR)
Tank Temperature
Chill-A , Chill-B , Chill-C Run Statuses
CWP and BCWP Run Statuses
SP and BSP Run Statuses
SP and BSP Run Speeds
All Faults / Alarms