Commercial Office Electrical Installation Design

Job ID: 39652965

Budget: $30 – $250 CAD

ACEL Graded Assignment #1


1.0​Details of Assignment

1.1​Design an electrical installation for a small Commercial office building unit​ using the drawing set as a guide

​1.2​Produce a floor plan diagram for the entire electrical installation

​1.3​The electrical installation shall show the use of a(n):

1.3.1​Electrical service - the size of service ​​for a commercial office building is determined using ​CEC Rule 8-210 and Table 14. Rule 8-210 (a) and Table ​14 are used to calculate the basic load for the building. If the ​actual installed load is greater than the basic load, the ​greater of the two loads shall be used to determine the size ​of service (Rule 8-106 (2)). Rule 8-210 (b) states that the ​special loads to be installed in the building shall be based on ​the rating of the equipment installed with any applicable ​demand factors as permitted by the Code. The ​total demand ​load for the building is the sum of calculated or installed ​basic load plus the special loads.

​​Determine the AWG size and type of conductors ​​required for entire electrical installation.





2.0​Drawings

​2.1​All drawings included in the drawing set must have a title block ​containing the following:

​2.1.1​The object(s) in the drawing
​2.1.2​Scale
​2.1.3​Drawn By
​2.1.4​Date

3.0​Evaluation Plan

​3.1​The assignment is worth 20% of the total mark for the course

4.0​Due Date

​4.1 ​The assignment is due on _________________.

​4.2​A 10% per day penalty will be applied to assignments that are ​handed in late

5.0​Additional Notes


​5.1​Assemble the assignment in the same order as the rubric - failure ​to do so will result in the loss of five (5) marks

​5.2 ​Do not use plastic covers over any pages or drawings


6.0​Appendix “A”

• List of Special loads
• Office area spec’s
​Distribution of Marks for the Assignment


Marks
Office electrical layout drawing - quality and accuracy of drawing

10
Legend of Symbols for the Electrical layout - complete and accurate

5
Service calculations with panel layout and luminaire schedule- for the entire Office- Show calculations (use example handouts provided in previous class’s, show code rules)

10
Office Floor Plan - quality of the drawing, accuracy of dimensions, correct use of object, extension and dimension lines

10
Legend of Symbols for the Office Floor Plan - complete and accurate

5
Parts list - Complete parts list for the entire electrical installation (need to see a minimum of 50 parts)

10


Total Marks
50


Appendix A


Office Area Spec’s

• scaled drawing, area of 250 to 300 m2
• include a reception area, cubicles, kitchen-nook with a sink and counters, storage room and both male and female washrooms.

Special loads
Electric baseboard heaters 208V / 5000 watt’s total
Electric Hot water tank. 208V / 2000 watt’s total
Espresso machine 120V 500 watts
Fridge 8A 120V
Electric Cook top 208V / 25A
Micro-wave 120V 15A
Kitchen Exhaust fan120V 5A
Window signage that is 3m long